Thermal Camera for Condition Monitoring & Early Fire Detection

FLIR A500f and A700f Advanced Smart Sensor Thermal Cameras are ideal for users who want built-in, on-camera analytics and alarm capabilities for outdoor condition monitoring and early fire detection applications.

These cameras can help companies protect assets, improve safety, maximize uptime, and minimize maintenance costs.

Featuring a protective housing designed to withstand harsh environmental conditions, FLIR A500f/A700f cameras combine unmatched thermal imaging with edge computing and industrial internet of things (IIoT) for simplified inclusion in new or existing networks.

For VMS integrations, thermal and visible streams can be viewed independently or simultaneously. The cameras are easy to add, set up, and operate in HMI/SCADA systems, offering automation system solution providers a running start.

We’re here to help you!

We are an official partner!

20+ years experience!

Call us to learn more!

Description

Fire Detection and Condition Monitoring for Industrial Facilities

For early fire detection, the A500f and A700f thermal cameras can quickly identify increased temperatures related to potentially dangerous conditions.

If smoke is present, the cameras can help provide increased awareness for decision makers to properly assess and address incidents. Both cameras feature Flexible Scene Enhancement (FSX) technology, found on Teledyne FLIR K-Series handheld firefighting devices. The result is an ultra-sharp, finer-textured image that shows subtler edge details supplied by the embedded visible camera onto the thermal image, enabling operators to recognize objects and people more easily.

The A500f/A700f are also effective tools for pile-burn monitoring, providing automated early warnings for potential issues in waste management facilities or coal collection areas that operate around the clock.

Manufacturing facilities, chemical processing locations, or power substations that use common communications and control language can also benefit from the A500f and A700f beyond fire detection. These cameras empower those organizations to reduce maintenance costs by identifying heat anomalies from mechanical problems early, thereby extending the life of plant components while maximizing uptime.

Effective Ruggedness and Thermal Range for Outdoor Applications

Featuring a protective IP67-rated housing designed to withstand temperatures between -30° to 50°C (-22° to 112° F), the A500f/A700f cameras are designed for harsh environments and discreet enough to deter from theft. In addition, the cameras use a single power-over-Ethernet (PoE) cable for both power and communication, helping to further minimize points of potential failure.

The A500f/A700f offers superior thermal imaging capability with a resolution of 464 x 348 (161,472) for the A500f and 640 x 480 (307,200) thermal pixel resolution for the A700f. Users can expect a ±2° C (±‐3.6° F) temperature measurement accuracy.

The A500f has a temperature detection range between -20° to 1500°C (-4° to 2732° F), while the A700f offers a temperature range of between 20° to 2000°C (68° to 3632°F) for detecting chemical fires and other extreme industrial fire conditions.

Along with thermal lens options ranging from 14° to 42° and an embedded HD visible camera, these devices fulfill the needs of most outdoor condition monitoring and fire detection applications.

Seamless Integration and Set Up

Installing the FLIR A500f/A700f cameras is seamless. Both cameras are ONVIF compliant and integrate easily into standard security VMS and NVR solutions including control of pan/tilts.

For VMS integrations, thermal and visible streams can be viewed independently or simultaneously. The cameras are easy to add, set up, and operate in HMI (Human Machine Interface) SCADA (supervisory control and data acquisition) systems, offering automation system solution providers a running start. Both the A500f and A700f fully support IIoT protocols such as MQTT (Message Queuing Telemetry Transport) and RESTful API with a system unique token key for extra security.

 

flir A500f A700f outdoor monitoring

For Outdoor Monitoring

The protective housing can withstand temperatures between -30° to 50°C, providing a high level of protection against challenging environmental conditions and theft.

flir A500f A700f integration

Simplify Integration

Multiple communication and control options enable easy integration into standard security and IiOT solutions including HMI/SCADA, ONVIF, Modbus, MQTT, and REST API protocol.

flir A500f A700f results

Consistent, Accurate Results

With up to 640 × 480 thermal resolution, remote motor focus, FSX® (Flexible Scene Enhancement) technology, and three fields of view, FLIR A500f / A700f cameras provide reliable measurements every time.

Specifications

System Overview A500f A700f
IR Resolution 464 × 348 (161,472 pixels) 640 × 480 (307,200 pixels)
Visual Resolution 1280 × 960
Detector Pitch 17 µm 12 µm
MSX® & FSX® Yes
Available Field of Views 14°, 24°, 42° athermalized lens
Focal Plane Array [FPA] Uncooled microbolometer
Focus Motorized focus, manual & on-command automatic (scene contrast method)
Image Frequency 30 Hz
Image Storage Records up to 100 FLIR radiometric JPEG; storage as function of: alarm, scheduling, or user interaction (camera web)
Measurement
Object Temperature
Range
-20°C to 120°C (-4°F to 248°F),
0°C to 650°C (32°F to 1202°F),
300°C to 1500°C
(572°F to 2732°F)
-20°C to 120°C (-4°F to 248°F),
0°C to 650°C (32°F to 1202°F),
300°C to 2000°C
(572°F to 3632°F)
Accuracy ±2°C (±3.6°F) or ±2% of reading, for ambient temperature
15°C-35°C (59°F-95°F) and object temperature above 0°C (32°F)
Readout Measurement results:
Ethernet/IP, Modbus TCP server (pull), Modbus TCP client (push), MQTT (push), REST API (GET/POST), measurements and still image (radiometric JPEG, visual 640 × 480, visual 1280 × 960), web interface
Automatic Hot and Cold Detection Max./min. temperature value and position shown within box
Measurement Presets Yes
Measurement Tools 10 spotmeters, 10 boxes or mask polygons, 3 Deltas (difference any value/reference/external lock), 2 isotherms (above/below/interval), 2 iso-coverage, 1 reference temperature, 2 lines, 1 polyline, Maximum 12 measurement functions at the same time
Web Interface Yes
Multi Streaming Yes
Alarm
Alarm Functions On any selected measurement function, digital in, and internal camera temperature
Alarm Output Digital out, e-mail (SMTP) (push), Ethernet/IP, file transfer (FTP) (push), Modbus TCP server (pull), MQTT (push), query over RESTful API (pull), store image or video
Encoding Video stream: H.264, MPEG4, or MJPEG Radiometric stream: Compressed JPEG-LS over RTSP
Digital Input/Output
Digital I_O Connector Type Terminal block inside housing
Digital I_O Isolation Voltage 500 VRMS
Digital Input Purpose NUC, NUC disable, alarm
Digital Inputs 2x opto-isolated, Vin(low)= 0–1.5 V, Vin(high)= 3–25 V
Digital Output Purpose As a function of alarm, output to external device, Fault (NC)
Digital Outputs 3x opto-isolated, 0–48 V DC, max. 350 mA; solid-state opto relay; 1x dedicated as Fault output (NC)
Cable Glands 1x M12, 1x M16, 1x M20
Ethernet
Ethernet For control, result, image, and power
Ethernet Communication TCP/IP socket-based FLIR proprietary
Ethernet Connector Type IP67 rated RJ45 port
Ethernet Interface Wired
Ethernet Power Power over Ethernet, PoE IEEE 802.3af class 3 EtherNet/IP, IEEE 1588, Modbus TCP, MQTT, SNMP, TCP, UDP, SNTP, RTSP, RTP, HTTP, HTTPS, ICMP, IGMP, sftp (server), FTP (client), SMTP, DHCP, MDNS (Bonjour), uPnP, PoE injector sold separately
Environmental Data
Operating Temperature Range -30°C to 50°C (-22°F to 122°F)
EMC EN50130-4, EN61000-6-3, EN55022 Class B, FCC Part. 15 Class B
Encapsulation IP67
Physical Data
Packaging Size [L x W x H] 62 cm × 20.2 cm × 22 cm (24.41 in × 7.92 in × 8.66 in)
Size [L x W x H] 51.5 cm × 17.7 cm × 22.9 cm (20.28 in × 6.97 in × 9.02 in)
Mounting Sold separately, pole and wall adapters available
Housing Material Aluminum housing, sunshield in ABS
System Features
Heater 8W, electronically controlled, T_ON 20°C ±2°C (68°F ±4°F),T_OFF 23°C ±2°C (73.4°F ±4°F)
ONVIF Conformance Yes. ONVIF Profile S
Window Transmission Automatic, based on window temperature
Power Consumption 30W PoE, PoE+, Type 2. IEEE 802.3af, IEEE 802.3at/PoE Plus